INFLUENCE OF WIND TURBINE GENERATOR ON THE SHORT-CIRCUIT CURRENT BETWEEN PHASES THROUGH CABLE SCREENS OF A WIND FARM IN 10-35 kV POWER NETWORKS
st7 (Українська)

Keywords

cable power line
cable shield
double earth fault current

How to Cite

Buinyi, R.O., et al. “INFLUENCE OF WIND TURBINE GENERATOR ON THE SHORT-CIRCUIT CURRENT BETWEEN PHASES THROUGH CABLE SCREENS OF A WIND FARM IN 10-35 KV POWER NETWORKS”. Proceedings of the Institute of Electrodynamics of the National Academy of Sciences of Ukraine, no. 56, Aug. 2020, p. 034, doi:10.15407/publishing2020.56.034.

Abstract

Shown the principle for calculation of double-fault ground current on a branch of electric power network with two sources (one of the sources can be a wind electric plant while the other source can be a power line). In cable shields with double ground fault the currents will be from the two sources. Thus, all the sources should be taken into account for calculation the ground fault currents and selection of the cable’s shield cross-section. Analyzed the influence of power network specifications on double-fault ground current and shown that such an influence is small, except the correspondence between subtransient currents of triple faults on both sides of the cable power line. In case of grounding the cable shields from one side of the power line, the full current of the double fault will flow through the single-core cable. So, it will require using cables with substantially larger cross-sections. It is found that the dissipation resistance of electric ground of cable shields does not significantly affect the double-fault ground current. References 5, figures 4.

https://doi.org/10.15407/publishing2020.56.034
st7 (Українська)

References

Dmytryev M.V. Grounding of the shields of single-phase power cables with the voltage 6-500kV. SPb.: Zavod energozashitnyh ustrojstv, 2008. 54 p. (Rus)

Buinyi R.O., Zorin V.V., Kvytsynskyi A.O. About definition of critical length of a cable electric power line. Comments and remarks to chapter 2.3 of rules of electric installations. Visnik Nacionalnogo tehnichnogo universitetu Harkivskij politehnichnij institut. 2010. No 36. Pp. 19-26. (Ukr)

Buinyi R.O., Zorin V.V., Kvytsynskyi A.O. Calculation of thermal mode of cable lines made by single-core cable with insulation from cross-linked polyethylene. Energetika ta elektrifikaciya. 2011. No 4. Pp. 45-50. (Ukr)

Grinchenko V.S., Tkachenko A.O., Grinchenko N.V. Improving calculation accuracy of currents in cable shields at double-sided grounding of three-phase cable line. Elektrotehnika i elektromehanika. 2017. No 2. Pp. 39-42. DOI: https://doi.org/10.20998/2074-272X.2017.2.06 (Rus)

Rozov V.Yu., Tkachenko A.O., Erysov A.V., Hrynchenko V.S. Analytical calculation of magnetic field of three-phase cable lines with two-point bonded shields. Tehnichna elektrodynamika. 2017. No 2. Pp. 13-18. DOI: https://doi.org/10.15407/techned2017.02.013 (Rus)

Creative Commons License

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.

Copyright (c) 2023 Р.О. Буйний, І.В. Діхтярук, А.В. Красножон, А.О. Квицинський

Downloads

Download data is not yet available.