Abstract
The computations of the magnetic field generated by high-voltage (330 kV) underground power cable line with special fill-up soil having different dimensions (bulk) are carried out by the two- and three-dimensional computer models. The supplementary soil above the cables is the composite material with effective magnetic properties and serves as a magnetic shield. The computer results obtained by 2D and 3D models are compared. The efficiency of magnetic field shielding depending on the magnetic permeability, width, and height of the fill-up soil is studied. As revealed, there is the optimal small soil height for the best magnetic field mitigation on the top of the ground directly over the cable line. In addition, the width of the magnetic soil has an appreciable effect on shielding efficiency. The shielding of underground single-circuit three-phase power cable lines is efficient only when using the magnetic fill-up soil (or ordinary external screen made of magnetic materials) with enough small height. References 14, figures 7.
References
Shidlovskii A.K., Shcherba A.A., Zolotarev V.M., Podoltsev A.D., Kucheriava I.M. Extra-high voltage cables with polymer insulation. Kyiv: Institute of Electrodynamics, Ukrainian Academy of Sciences, 2013. 550 p. (Rus)
Makarov E.F. Handbook on 0,4–35 kV and 110–1150 kV power networks. Moskva: Papirus-Pro, 2004, vol. 3, 688 p.; Moskva: Papirus-Pro, 2005, vol. 4, 640 p. (Rus)
Technical guide on installation, testing and operation of modern extra-high-voltage cable lines. Kharkov: Maidan, 2017. 64 p. (Rus)
Podoltsev A.D., Kucheriava I.M. Multiphysics modeling in electrical engineering. Kyiv: Institute of Electrodynamics, Ukrainian Academy of Sciences, 2015, 305 p. (Rus)
Electric installation code. Minpalivo Ukrainy, 2010, 776 p. (Ukr)
Sergeant P., Dupre L., Melkebeek J. Magnetic shielding of buried high voltage cables by conductive metal plates. COMPEL. 2008. Vol. 27. No 1. Pp. 170–180. DOI: https://doi.org/10.1108/03321640810836735
Kucheriava I.M. Magnetic field shielding of underground power cable line by H-shaped shield. Tekhnichna Elektrodynamika. 2020. No 6. Pp. 15–20. (Rus) DOI: https://doi.org/10.15407/techned2020.06.015
Kucheriava I.M. Shielding of underground extra-high voltage cable line by plane ferromagnetic shield. Tekhnichna Elektrodynamika. 2019. No 6. Pp.13–17. (Rus) DOI: https://doi.org/10.15407/techned2019.06.013
Shcherba A.A., Podoltsev O.D., Kucheriava I.M. The magnetic field of underground 330 kV cable line and ways for its reduction. Tekhnichna Elektrodynamika. 2019. No 5. Pp. 3–9. (Rus) DOI: https://doi.org/10.15407/techned2019.05.003
Privezentsev V.A., Grodnev I.I., Kholodnyi S.D., Ryazanov I.B. Foundations of cable technologies. Moskva-Leningrad: Energiya, 1967. 464 p.
Lyach V.V., Molchanov V.M., Santatskii V.G., Kvitsinskii A.A. 330 kV cable line: some aspects of designing. Promelektro, 2009. No 6. Pр. 27–33. (Rus)
Podoltsev О.D., Kucheriava I.M. Three-dimensional model for computation of magnetic field of underground cable line. Pratsi Institutu Elektrodynamiki NAN Ukrainy. 2020. No 56. Pp. 16–19. DOI: https://doi.org/10.15407/publishing2020.56.016
Comsol multiphysics modeling and simulation software. – http://www.comsol.com/
Rozov V.Yu., Reutskiy S.Yu., Pelevin D.E., Yakovenko V.N. Investigation of magnetic field of high-voltage AC transmission lines. Tekhnichna Elektrodynamika. 2012. No 1. Pp. 3–9. (Rus)

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
Copyright (c) 2021 I.M. Kucheriava